Ningbo Rendong Transformer Co., Ltd.

3 phase oil-immersed distribution transformer

3 phase oil-immersed distribution transformer
Product Detailed

11kV 22kV 33kV oil-immersed ONAN ditribution transformer
Tender project distribution transformer
3phase oil filled transformer

Main Characteristics

1.Low no-load loss and energy conservation

2.Low noise and environmental protection

3.Long service lifetime and safe and reliable performance

4.Advanced structural design and exquisite craftsmanship

5.Appropriate protective measures

 

Normal Operation Conditions

1.Installation site: outdoors or indoors

2.Altitude: less than 1000M

 

3.Ambient temperature: -25oC~+40oC

 

4.Maximum relative humidity: 95%(25oC)

5.Earthquake-resistant capability: the horizontal acceleration of ground surface is 0.3g, and 

          the vertical acceleration of ground surface is 0.15g

          concurrently acting continuous three sine waves, safety factor ≥1.67

6.All-weather working capability in outdoor environment

7.The equipment has certain capability in dustproof, antifouling, waterproof, earthquake resistance and shock resistance

 

Note: Transformers operating in special environment are available upon the demand of customers.

 

 

 

S(B)9-M(RL)-10~3150/10,6  

Performance Parameter List

 

Rated

capacity

(kVA)

Voltage combination and tap range

Connection

Group

No-load

loss

(W)

 

75°C load loss

(W)

No-load

current

(%)

Impedance

voltage

(%)

High voltage

(kV)

Tap

(%)

Low

voltage

(kV)

10

6

6.3

6.6

10

10.5

11

±5

±2×2.5

0.4

0.69

Yyn0

Dyn11

Yzn11

70

310/325

3.20

4.0

20

100

480/500

3.00

30

130

600/630

2.80

50

170

870/910

2.50

63

200

1040/1090

2.40

80

250

1250/1310

2.20

100

290

1500/1580

2.10

125

340

1800/1890

2.00

160

400

2200/2310

1.90

200

480

2600/2730

1.80

250

560

3050/3200

1.70

315

670

3650/3830

1.60

400

800

4300/4520

1.50

500

960

5150/5410

1.40

630

1200

6200

1.30

4.5

800

1400

7500

1.20

1000

1700

10300

1.10

1250

1950

12000

1.00

1600

2400

14500

0.90

2000

2650

17400

0.80

5.0

2500

3200

20200

0.70

3150

3800

24000

0.60

Note: 1. Load loss values above the oblique line in the table are applicable to the Yyn0 connection group, and the values below the oblique line are applicable to the Dyn11 or Yzn11 connection group. 

         2. The list shows main performance parameters of a three-phase duplex winding off-circuit-tap-changing distribution transformer. Customized transformers of different specification are available upon the demand of users.

 